Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/16/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ONLY ONE CONDUCTOR TO GROUND LUG 2. RECEPTACLE TO BE MOUNTED TO INDUSTRIAL COVER 3. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANEL BOTTOM 4. PROPERLY GROUND CONTACTOR ENCLOSURE 5. PLEASE VERIFY LISTING FOR AIR COMPRESSOR 6. FINISH INSTALL OF MOTION SENSOR COVER 7. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO -- 406.8 8. SEAL UNUSED CONDUIT OPENING |