Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GROUNDING ELECTRODE CONDUCTOR TO BE AS PER 250.64 2. BOND ENCLOSURE ROOF: 1. SHEETMETAL THREAD SCREWS NOT ALLOWED 250.8 2. ONLY ONE CONDUCTOR PER LUG TERMINATION |
|
| 07/25/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED ELECTRICIAN ON SITE 2. GO OVER REQUIREMENTS OF ART. 690 & 250 & 230 OF THE NEC 2005 EDITION |
|
| 07/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED TO HAVE APPROVED PLANS ON SITE EQUIPMENT TO BE OPENED FOR INSPECTION |