Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04427
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORY TO BE NEAT, CORRECT & LEGIBLE - NEC 408.4 2. EMERGENCY LIGHTS TO BE AIMED DOWN & OUT SO THEY WILL BE EFFECTIVE IF NEEDED - NEC 110.3B ON ROOF 1. NEW AC DATA PLATE TO BE IDENTIFIED 2. IDENTIFY UNIT ITSELF AS IS IN PANEL DIRECTORY 3. GROUND DISCONNECT 4. SEAL UNUSED OPENING IN DISCONNECT 5. ROUTE LINE CONDUCTORS SO THEY ARE NOT IN FRONT OF FUSES 4C3 1. IDENTIFY DATA PLATE, FUSES TO BIG, MULTIPLE CONDUCTORS NOT ALLOWED UNDER SAME LUG, PIPE INSTEAD OF FLEX, SECURE TO EQUIPMENT TO ROOF GROUND DISCONNECT |
|
| 02/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS SHOW E-LIGHTS @ EXIT - NOT JUST SIGN 2. PLANS SHOW "NEW" RTU#4 3. NEED TO SHOW REVISED PLAN TO SHOW ACTUAL SCOPE OF WORK - NO FURTHER INSPECTION AT THIS TIME |