Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM04411

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/18/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/17/2008 PLUMBING - INTERMEDIATE Cancelled
01/16/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :$
- ABOVE CEILING PIPING IS NOT PROPERLY SUPPORTED
SEE UPC TABLE 3-2
- REVENT HAS BACK PITCH. ROUTE IN A WAY THAT WILL CORRECT SLOPE
- A MISSION COUPLING LISTED FOR PLASTIC TO PLASTIC IS REQUIRED AT VENT CONNECTION
- SEAL JOINTS IN PIPE INSULATION PER NOTE #5
- FAILURE TO COMPLY WILL RESULT IN REINSPECTION FEES
- FOR FINAL TURN ON WH AND ADJUST TEMPERATURE AT MIXING VALVE.
01/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST DWV OK & WATER PIPING OK IN WALL ONLY
1. SUPPORT OVERHEAD VENT & WATER PIPING IN WATER HEATER AREA
2. SEE NOTE #5 FOR INSULATION ON HOT WATER PIPING
3. PROVIDE APPROVED COUPLING FOR CONNECTION AT EXISTING VENT.

NOTE: VENT PIPING TO RUN LEVEL OR GRADE BACK TO SANITARY SEWER SYSTEM