Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM04411
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/18/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/17/2008 | PLUMBING - INTERMEDIATE | Cancelled | ||
01/16/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :$ - ABOVE CEILING PIPING IS NOT PROPERLY SUPPORTED SEE UPC TABLE 3-2 - REVENT HAS BACK PITCH. ROUTE IN A WAY THAT WILL CORRECT SLOPE - A MISSION COUPLING LISTED FOR PLASTIC TO PLASTIC IS REQUIRED AT VENT CONNECTION - SEAL JOINTS IN PIPE INSULATION PER NOTE #5 - FAILURE TO COMPLY WILL RESULT IN REINSPECTION FEES - FOR FINAL TURN ON WH AND ADJUST TEMPERATURE AT MIXING VALVE. |
|
01/07/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST DWV OK & WATER PIPING OK IN WALL ONLY 1. SUPPORT OVERHEAD VENT & WATER PIPING IN WATER HEATER AREA 2. SEE NOTE #5 FOR INSULATION ON HOT WATER PIPING 3. PROVIDE APPROVED COUPLING FOR CONNECTION AT EXISTING VENT. NOTE: VENT PIPING TO RUN LEVEL OR GRADE BACK TO SANITARY SEWER SYSTEM |