Permit: T07CM04407

Parcel: 11307242F


Addresses:

2902 N MOUNTAIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/03/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FIXTURES TO HAVE PROPER ROMEX CONNECTOR OR J-BOX
2. NEED SINGLE RECEPTACLE OR GFI PROTECTION AT WASHER
3. J-BOX BUSHING TO GO INTO BOX - NOT SIDING

*THERE WILL BE A FEE IF NOT CORRECT NEXT INSPECTION
11/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY CKTS
2. NEED BREAKER BLANKS
3. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND LUG
REMOVE PAINT UNDER LUG
4. RECEPTACLES SHOW OPEN GROUND
11/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CKT'S TO PROPERLY CONNECT TO INDIVIDUAL BREAKERS
2. IDENTIFY CKT'S ON PANEL DIRECTORIES
3. MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES
4. NEED PROPERLY SIZE EQUIPMENT GROUND RAN WITH NEW CKTS
5. GROUND J-BOXES
6. NEED ROMEX CONNECTORS FOR ENTRY INTO J-BOXES
7. PROVIDE SINGLE RECEPTACLE FOR WASHER, GFI RECEPTACLE FOR DUPLEX