Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK UPGRADE & GROUNDING BY NET ELECTRIC 2. OBTAIN PERMIT FOR SERVICE UPGRADE TO FINAL OUT THIS PERMIT, YOU MAY POSSIBLY ADD TO THIS PERMIT - 4 METERS TOTAL |
|
| 07/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BLD. LOCKED RECALL INSP. 1. BOND BUSHINGS OR BONDING TYPE LOCKNUTS REQUIRED AT SERVICE AHEAD OF OVERCURRENT DEVICE PER 250 NEC 2. CANNOT MULTI-TAP MORE THAN ONE TAP OFF OF SPLIT BOLTS 3. SERVICE IS PARTIALLY UPGRADED, VERIFY WATER AND GAS BOND SERVICE DISCONNECT REPLACED TO HIGH, 6'7" MAX. HEIGHT TO CENTER OF HANDLE |