Permit: T07CM04398

Parcel: 135061190

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/08/2008 FRAMING Approved IVRS - Inspection :*
12/17/2007 FRAMING Partial Approval IVRS - Inspection :*
1) INSTALL NAIL STOPS THRU-OUT
2) EXPOSE OR INSTALL GROUND RODS
3) BOND GAS
4) T/P LINE MUST BE HARD PIPED WITH OUT FLEX
5) NO TAPE PERMITTED SINGLE WALL TO B-VENT
6) WATER HEATER VENT HAS NEGATIVE PITCH
7) 1" CLEARANCE REQUIRED B-VENT TO COMBUSTIBLE
8) RAISE CONDENSATE DRAIN VENT ABOVE CUT OFF SWITCH
9) EXHAUST FANS THRU ROOF