Permit: T07CM04396

Parcel: 12709012E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04396

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. USE APPROVED AS PER LISTED WIRE MOLD BOX
2. WAITING ON REVISIONS OF PAPERWORK
12/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH PREVIOUS ITEMS 4, 5, 6 AND 7
12/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE APPROVED EXTENDER RINGS - METAL NOT APPROVED
AT COMBUSTIBLES - 110.3
2. WHERE IS GROUND PER 800.40 AS PER PLANS
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RING - 314.20
4. SUPPORT M/C CABLES AS PER CODE -- 330.30
5. BOX OVERFILLED 314.16
6. CIRCUITS NOT RUN AS PER PLANS - INSTALL AS PER PLANS OR REVISE FOR PANEL LOADS & CIRCUITS
7. REVISE PANEL DIRECTORIES AS PER 408.4

PLEASE OPEN CEILING FOR ALL CUT-IN BOXES
12/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
INSTALL ALL OUTLETS
NEED TO SEE OFFICE FURNITURE CONNECTIONS