Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04396
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/12/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. USE APPROVED AS PER LISTED WIRE MOLD BOX 2. WAITING ON REVISIONS OF PAPERWORK |
|
12/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS 4, 5, 6 AND 7 |
|
12/10/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED EXTENDER RINGS - METAL NOT APPROVED AT COMBUSTIBLES - 110.3 2. WHERE IS GROUND PER 800.40 AS PER PLANS 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RING - 314.20 4. SUPPORT M/C CABLES AS PER CODE -- 330.30 5. BOX OVERFILLED 314.16 6. CIRCUITS NOT RUN AS PER PLANS - INSTALL AS PER PLANS OR REVISE FOR PANEL LOADS & CIRCUITS 7. REVISE PANEL DIRECTORIES AS PER 408.4 PLEASE OPEN CEILING FOR ALL CUT-IN BOXES |
|
12/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSTALL ALL OUTLETS NEED TO SEE OFFICE FURNITURE CONNECTIONS |