Permit: T07CM04394

Parcel: 122010740

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
SPACE BEING OCCUPIED
11/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL SCHEDULE TO BE AS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
USE APPROVED EXTENDER RING
3. CABLES TO BE SUPPORTED INDEPENDENT OF
GRID WIRE 300.11 AND ATTACHED AT BOTH ENDS
4. VDV CABELING TO BE SUPPORTED
AS PER 725.6, 800.6 & 300.11
5. REMOVE TILE TO FINISH INSPECTION
6. PLEASE BRING IN EQUIPMENT TO VERIFY LISTING LABELS
7. REVISE PANEL SCHEDULE TO REFLECT ACCURATELY WHAT IS INSTALLED.