Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/29/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 11/28/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL TIE WIRE TO LIGHTING FIXTURES 2. LIGHTING FIXTURES TO BE SECURED TO GRID 3. SEAL OPEN KNOCKOUTS IN JUNCTION BOXES 4. TIE WIRES USED FOR SUPPORT OF MC CABLES TO BE SECURED AT BOTH ENDS |