Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* - RELOCATE DUCT SMOKE DETECTORS TO CENTER OF PLENUM - INSULATE SHEETMETAL ELBOWS - PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT DETECTORS - PRETEST DETECTORS WITH SMOKE - OK FOR CEILING TILES - WILL CHECK FINAL CONDENSATE CONNECTIONS ABOVE CEILING ON FINAL - PROVIDE AIR BALANCE REPORT FOR FINAL |
|
| 02/19/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPLY & EXHAUST IN RESTROOMS OK TO SHEETROCK OK TO INSULATE CONDENSATE |
|
| 02/15/2008 | MECHANICAL - ABOVE CEILING | Cancelled | IVRS - RI canceled |