Permit: T07CM04393

Parcel: 130140250


Addresses:

4192 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/21/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS MADE OK
PLUMBING FINAL OK
03/19/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR TO PAY REFEE FOR FAILURE TO COMPLY WITH NOTES LEFT ON 3/13/08 AND 3/18/08

PRIOR TO HAVING FINAL PLUMBING INSPECTION
03/18/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
USE APPROVED MEANS TO SUPPORT & SECURE EXPANSION TANK AT WATER HEATER
03/13/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. WATER HEATER EXPANSION TANK REQUIRES SUPPORT AND SECURE
2. PROVIDE FULL SIZE RIDGID PIPING FOR TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING (NO FLEX)
3. MAKE LAUNDRY TUB WATER TIGHT AT WALL
4. INSULATE MINIMUM 8' IN & 8' OUT OF WATER HEATER TO MEET 2006 ENERGY CONSERVATION CODE
5. PUBLIC USE LAVS REQUIRE A MEANS BESIDES THE WATER HEATER TO LIMIT HOT WATER TEMPERATURE TO 110 DEG. SEE NOTE #14