Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR TO RESCHEDULE |
|
| 03/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL NEUTRAL CONDUCTOR TO WATER HEATER 2. INSTALL PROPER SIZE OVERCURRENT PROTECTION FOR WATER HEATER 3. NEED DETAILED PANEL SCHEDULES 4. INSTALL ALL MOUNTING SCREWS FOR RECEPTACLES IN INDUSTRIAL COVERS 5. NO POWER TO ROOFTOP GFI. PROPERLY SUPPORT/SECURE BOX INSTALL BUBBLE COVER 6. INSTALL PROPER SIZE FUSES ON RTU 7. INSTALL PROTECTIVE BUSHINGS ON CONDUCTORS #4 AND LARGER 8. INSTALL GROUND BOXES IN PANELS GROUND & NEUTRALS TO BE SEPARATE 9. NOT ALL EM LIGHTS WORKING |