Permit: T07CM04393

Parcel: 130140250


Addresses:

4192 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/04/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
02/15/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL FAR SIDE SUPPORT ON BOXES
2. REMOVE MC CABLE FROM INSIDE STUD CHANNELS
3. MC CABLE TO BE SUPPORTED WITHIN 12" OF BOXES
4. CANNOT USE SHEETMETAL SCREWS FOR CONNECTION OF GROUNDS TO METAL BOXES
5. INSTALL PROPER MUD RINGS FOR 5/8" ROCK
SHOULD BE 3/4" MUD RINGS.
6. OK HARD LIDS