Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
| 02/15/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL FAR SIDE SUPPORT ON BOXES 2. REMOVE MC CABLE FROM INSIDE STUD CHANNELS 3. MC CABLE TO BE SUPPORTED WITHIN 12" OF BOXES 4. CANNOT USE SHEETMETAL SCREWS FOR CONNECTION OF GROUNDS TO METAL BOXES 5. INSTALL PROPER MUD RINGS FOR 5/8" ROCK SHOULD BE 3/4" MUD RINGS. 6. OK HARD LIDS |