Permit: T07CM04387

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM04387

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
FLANGES OK
YOU MAY RE-COVER WALLS AFTER ISOLATING THE CW PIPING THAT IS TOUCHING METAL
07/29/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CLOSET FLANGES SHALL NOT MOVE UP AND DN OR
SIDE TO SIDE.
2. OPEN WALLS AT TRMS 540

I CAN SEE CU TOUCHING METAL AND ISOLATORS THAT ARE NOT SECURED AND HAVE SLID OUT OF HOLES
05/14/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV TEST OK
STILL NEED SOME SLOPE CORRECTIONS, PROVIDE 2% SLOPE
05/09/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE MIN. REQUIRED SLOPE
PROVIDE P-TRAP ON MOP SINK
PROVIDE CORRECT SIZE VENT AND CLEANOUT
PROVIDE PROPER FITTINGS ON VENTS BELOW FLOOD LEVEL
VENT TAKE-OFFS SHALL BE AT A TRUE 45 DEG.
PSI TEST ON WATER, OK TO INSULATE
SUPPORT, SECURE, ISOLATE