Permit: T07CM04386

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/04/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/16/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
NEED TO SEE CLOSET FLANGES ONLY
04/10/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- TEST ON VENTS OK
- CORRECT VENT LOCATION AT MS 417 AND INSTALL WALL BRACKET BACKING AND SAFETY PLATE AT FLOOR
- INSTALL RISER CLAMP AT 4" RISER IN COL AT NOTES 11 & 12
- NEED RISER CLAMPS ON ALL LEVELS. RECALL INSP.
04/09/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV TO ABV CEILING OK
ADD SUPPORTS AS REQUIRED
03/05/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNUSED CAPPED WATER PIPING BRANCHES
REQUIRE NON-FERROUS PLUGS

100 PSI AIR TEST OK
OK TO INSULATE PER SPEC.
WILL REINSPECT FOR STRAPPING AND SUPPORTS
AFTER INSULATION IS COMPLETE
03/03/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. REPAIR LEAK - LIST NOT COMPLETE