Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM04386
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/04/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/16/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEED TO SEE CLOSET FLANGES ONLY |
|
04/10/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - TEST ON VENTS OK - CORRECT VENT LOCATION AT MS 417 AND INSTALL WALL BRACKET BACKING AND SAFETY PLATE AT FLOOR - INSTALL RISER CLAMP AT 4" RISER IN COL AT NOTES 11 & 12 - NEED RISER CLAMPS ON ALL LEVELS. RECALL INSP. |
|
04/09/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV TO ABV CEILING OK ADD SUPPORTS AS REQUIRED |
|
03/05/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNUSED CAPPED WATER PIPING BRANCHES REQUIRE NON-FERROUS PLUGS 100 PSI AIR TEST OK OK TO INSULATE PER SPEC. WILL REINSPECT FOR STRAPPING AND SUPPORTS AFTER INSULATION IS COMPLETE |
|
03/03/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. REPAIR LEAK - LIST NOT COMPLETE |