Permit: T07CM04386

Parcel: 13317064B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04386

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/27/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/20/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. LABEL DISCONNECTS FOR LOAD SERVED
2. INSTALL PROPER COVER ON 100 AMP. DISCONNECT
HAVE SHARP CORNERS
3. EQUIPMENT LISTED AND LABELED
09/25/2008 ELECTRIC - FINAL Partial Approval NEED TO SEE X-RAY EQUIPMENT TO CHECK CONNECTIONS AND VERIFY LISTING

OK SUITE EXCEPT X-RAY EQUIPMENT
09/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH CONNECTION OF OFFICE FURNITURE
2. BOXES MORE THAN 1/4" -- 314.20
3. PANEL DIRECTORY 408.4 -- NO ABBREVIATIONS
4. FINISH ROOM 430 X-RAY

OK TO STOCK FURNITURE ONLY