| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/05/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE TRAP SEAL PROTECTION AT S.EQUIPT. FS 2. EXTERIOR VTR SHALL BE 10' ABV GRADE 906.4 AAV REQUIRES PLAN REV. 3. HB VAC BREAKER MISSING AT VAULT SINK 4. LEAK AT SINK IN RM. 185 5. YOU HAVE AN APPARENT CROSS CONNECTION AT YOUR WATER SUPPLIED EQUIPMENT LOCATED IN EXT. EQUIPT. YARD 6. PROVIDE A DETAIL OF SUPPLY PIPING AND OR A LISTING FOR YOUR EQUIPT. OR ELIMINATE UPSTRM CONN. ALSO, CERTIFY RP. 7. TEST WATER PER UPC 609.10 IF ANY CHEMICALS ARE IN EQUIPT. ALSO, TEST FOR CHEMICALS. 8. MED. GAS TESTING |