Permit: T07CM04383

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM04383

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
12/05/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE TRAP SEAL PROTECTION AT S.EQUIPT. FS
2. EXTERIOR VTR SHALL BE 10' ABV GRADE 906.4
AAV REQUIRES PLAN REV.
3. HB VAC BREAKER MISSING AT VAULT SINK
4. LEAK AT SINK IN RM. 185
5. YOU HAVE AN APPARENT CROSS CONNECTION AT YOUR WATER SUPPLIED EQUIPMENT LOCATED IN EXT. EQUIPT. YARD
6. PROVIDE A DETAIL OF SUPPLY PIPING AND OR A LISTING FOR YOUR EQUIPT. OR ELIMINATE UPSTRM CONN. ALSO, CERTIFY RP.
7. TEST WATER PER UPC 609.10 IF ANY CHEMICALS ARE IN EQUIPT. ALSO, TEST FOR CHEMICALS.
8. MED. GAS TESTING