Permit: T07CM04383

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - MEDICAL GAS/TEST

Date Description Inspector Results Comments
12/15/2008 PLUMBING - MEDICAL GAS/TEST Approved IVRS - Inspection :*
07/14/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LOW PSI TEST HOLDING 80
NEED PIPE LABELS
07/10/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
OUTLETS & INLETS INSTALLED
PROVIDE LOW PSI TEST
07/09/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
INSTALLING OUTLET BOXES
07/07/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
INITIAL TESTING OK
WORK NOT COMPLETE
07/02/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1. NO WORK ON MED GAS TODAY
2. TEST STILL HOLDING
07/01/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1. NO ONE WORKING ON MED GAS
2. PSI 150 TEST ONLY TEST OK
3. PROVIDE TESTING REPORT FROM STEVE GIBBONS
06/25/2008 PLUMBING - MEDICAL GAS/TEST Cancelled IVRS - RI canceled
06/23/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
06/20/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
06/19/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1. CHECKED MED GAS GANG BOX
2. MAKING DROP FOR VACUUM
CHECKED DAILY LOG
DON'T FORGET TO INCLUDE DAILY BLOW DOWN, PURGES, ETC.
06/17/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
VAC TO 2ND ZONE VALVE
06/16/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
INSTALLING VAC TUBING W/CLEANED & CAPPED PIPE AND FITTINGS
06/13/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
INSTALLING O2
06/12/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
06/11/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
REMOVE SHEETROCK AT ZONE VALVE WHERE CLEARANCE IS NEEDED FOR BRAZING AND INSPECTION OF MED. GAS PIPING
06/10/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
BEGIN 02 PIPING
06/09/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
DO NOT ONE SIDE WALLS WHERE THERE IS PIPING THAT HAS
NOT BEEN TESTED; ZONE VALVES AND OUTLETS
06/06/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
LOG BOOK, GANG BOX, MATERIALS, PURGE CHECKED OUT OK
06/05/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
1 INSTALLER AND 1 HELPER WORKING ON MA AND ZONE VALVE AND OUTLET BOX INSTALLATION
06/04/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
CALL FOR DAILY INSPECTIONS OF MED GAS INSTALLATION
GANG BOX AND FITTINGS OK
06/03/2008 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
MATERIALS OK
MAINTAIN LOG BOOK AND KEEP IT IN OFFICE TRAILER