Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
Permit Number - T07CM04383
Inspection Description - PLUMBING - MEDICAL GAS/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2008 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* | |
07/14/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* LOW PSI TEST HOLDING 80 NEED PIPE LABELS |
|
07/10/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* OUTLETS & INLETS INSTALLED PROVIDE LOW PSI TEST |
|
07/09/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* INSTALLING OUTLET BOXES |
|
07/07/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* INITIAL TESTING OK WORK NOT COMPLETE |
|
07/02/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1. NO WORK ON MED GAS TODAY 2. TEST STILL HOLDING |
|
07/01/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1. NO ONE WORKING ON MED GAS 2. PSI 150 TEST ONLY TEST OK 3. PROVIDE TESTING REPORT FROM STEVE GIBBONS |
|
06/25/2008 | PLUMBING - MEDICAL GAS/TEST | Cancelled | IVRS - RI canceled | |
06/23/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
06/20/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
06/19/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1. CHECKED MED GAS GANG BOX 2. MAKING DROP FOR VACUUM CHECKED DAILY LOG DON'T FORGET TO INCLUDE DAILY BLOW DOWN, PURGES, ETC. |
|
06/17/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* VAC TO 2ND ZONE VALVE |
|
06/16/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* INSTALLING VAC TUBING W/CLEANED & CAPPED PIPE AND FITTINGS |
|
06/13/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* INSTALLING O2 |
|
06/12/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
06/11/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* REMOVE SHEETROCK AT ZONE VALVE WHERE CLEARANCE IS NEEDED FOR BRAZING AND INSPECTION OF MED. GAS PIPING |
|
06/10/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* BEGIN 02 PIPING |
|
06/09/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* DO NOT ONE SIDE WALLS WHERE THERE IS PIPING THAT HAS NOT BEEN TESTED; ZONE VALVES AND OUTLETS |
|
06/06/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* LOG BOOK, GANG BOX, MATERIALS, PURGE CHECKED OUT OK |
|
06/05/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* 1 INSTALLER AND 1 HELPER WORKING ON MA AND ZONE VALVE AND OUTLET BOX INSTALLATION |
|
06/04/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* CALL FOR DAILY INSPECTIONS OF MED GAS INSTALLATION GANG BOX AND FITTINGS OK |
|
06/03/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* MATERIALS OK MAINTAIN LOG BOOK AND KEEP IT IN OFFICE TRAILER |