Permit: T07CM04383

Parcel: 13317064B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04383

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2008 ELECTRIC - FINAL Approved MRI EQUIPMENT NOT TO BE INSTALLED
12/16/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- THIS IS PARTIAL FINAL BECAUSE MRI ROOM IS NOT COMPLETE REST OF FLOOR IS COMPLETE.
- SEE LEERAY FOR FINAL APPROVAL IF MRI ROOM IS TO BE PERMITTED SEPARATELY.
12/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED COPY OF UL FIELD REPORT
12/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. UL DID FIELD EVALUATION ON X-RAY GENERATOR WAITING FOR REPORT FROM UL
2. VERIFIED FIELD EVALUATION STICKERS INSTALLED
3. CHECK WITH BUILDING INSPECTOR FOR TCO
4. I HAVE NO ISSUES
11/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. STILL NEED ARC FLASH STICKERS
2. STILL NEED FIELD EVALUATION FOR X-RAY GENERATOR
3. THIS IS PARTIAL FINAL FOR SPACE 105 NOT TO INCLUDE MRI AREA, MRI AREA NOT TO BE OCCUPIED
4. NEED TO CHECK WITH BUILDING INSPECTOR FOR TCO
11/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. EXITS & EMS TO BE PER PLAN
2. EVALUATION OF UNLISTED EQUIPMENT TO BE DONE BY NATIONALLY RECOGNIZED TESTING LABORATORY
3. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTIONS
11/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT VDV CABLING
2. RECIRCULATING PUMPS CORD ABOVE CEILING 400.7 & 8
3. USE APPROVED COVERS FOR E-STOPS
4. BOND BUSHING PER 250.97
5. FINISH 1, 3 & 4 PREVIOUS INSPECTIONS
11/06/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1ST FLOOR NORTH ONLY
1. PUT ARC FLASH STICKERS
2. ENSURE TEMP POWER IS REMOVED AND SEALED
3. CANNOT VERIFY LABEL FOR X-RAY GENERATOR
4. DUCT WORK IN DEDICATED SPACE NEEDS TO BE MOVED
11/05/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SOUTH SIDE
1. INSTALL SEISMIC WIRES ON ALL LIGHT FIXTURES
2. ATTACH ALL LIGHT FIXTURES TO GRID
3. CLOSE OPEN JUNCTION BOXES
SEAL OPEN KNOCKOUTS