Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED BACTERIA REPORT BUILDING INSPECTOR TO RECEIVE (1) IN-HOUSE BACKFLOW CERTIFICATION GAS CARD AT METER |
|
| 08/11/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE BACKFLOW CERTIFICATION, BACTERIA REPORT AND VACUUM BREAKER AT FRONT HOSE |
|
| 08/08/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MORE THAN 90 DEG. CHANGE OF DIRECTION ON A TRAP ARM REQUIRES A CLEANOUT 2. MORE THAN FIVE FEET ON INDIRECT WASTE REQUIRES A DIRECT TRAP 3. EACH WATER SUPPLIED EQUIPMENT TO HAVE BACKFLOW PROTECTION CHECK AIR GAPS (GRATES, STRAINERS) 4. WILL NEED TO SEE PRESSURE TEST ON ENTIRE SYSTEM ALSO, SAFETY CHECK ON EXISTING SYSTEM |