Permit: T07CM04373

Parcel: 12404032B


Addresses:

1443 E 1ST ST

Inspection Status: Partial Approval

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/30/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CLOSET BEND MAY NOT HAVE A FOULING LEDGE
2. CAP OFF ALL OPEN DRAIN PIPING
07/30/2008 PLUMBING - INTERMEDIATE Approved
06/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND FLOOR RESTROOMS OK TO COVER FLOOR AND WALLS
06/25/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. GAS PRESSURE TEST OK
2. OK TO COVER WALLS FIRST FLOOR
06/24/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. INSTALL AVB's ON ALL HOSE BIBS
2. FINISH STRAPPING PIPE AND SUPPORT ALL STUB OUTS

CONTINUED "NOT READY" WILL RESULT IN A
REINSPECTION FEE
06/23/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ABS DWV TO ABOVE CEILING WATER TEST OK
2. STRAP VERTICAL PIPING
3. I BELIEVE YOUR 2" VENT IS OVERLOADED ONLY 24 DFU's ALLOWED ON 2" VENT