Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SECURELY ATTACH FIXTURES TO GRID 410.16 IF SCREWS - 4 ON CORNERS OR 2 ON CENTER 2. CANNOT USE SHEETMETAL SCREWS FOR GROUNDING - 250.8 3. USE APPROVED STRAPS FOR MC 4. SUPPORT VDV CABLING 725.24, 760.24, 800.11, 300.11 |
|
| 06/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. MOVE OVER RECEPTACLES BY BAR SINK PER PLAN 2. INSTALL NAIL PLATES AS NEEDED 3. DEMO OLD WIRING BEFORE COVER |
|
| 06/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PLEASE ADD 02010 TO PERMIT OK 2 - 3/4" PVC CONDUITS FROM DINING ROOM TO ADA BATHROOM |