Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* BE ADVISED THERE ARE 2 OTHER NON-FINALED PERMITS OPEN AT THIS LOCATION, MUST BE APPROVED. |
|
| 08/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK U.G., INSTALL MARKER TAPE IN TRENCH PER NEC. 300 FOR UTILITY POWER TO X-FORMER |
|
| 07/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT USE SHEET METAL SCREWS FOR GROUND BAR ATTACHMENT 2. SERVICE CONDUCTORS NOT SIZED PROPERLY FOR 200 AMP SERVICE TO BE 3/0 COPPER 3. MAIN BONDING JUMPER AND OTHER BONDING JUMPERS NOT SIZED PROPERLY. PREVIOUS INSPECTION ITEM 4. AIC RATING TO BE 22 KAIC WHAT IS AVAILABLE FAULT CURRENT FROM TEP X-FMR 5. 2 1/2" PVC TO BE 24" DEEP MIN. 6. MARK SERVICE DISCONNECT |
|
| 07/22/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MAIN BOND JUMPR AND BOND WIRE AHEAD OF OVERCURRENT PROTECTION TO BE SIZED PER 250.66 NEC & PER 250.28 |
|
| 07/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEUTRAL MUST BE BONDED WITH MAIN BOND JUMPER PER 250 NEC - SEE NOTE #1 INSP. 7/14/08 |
|
| 07/14/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 07/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL MAIN BONDING JUMPER IN SERVICE PANEL 2. PROVIDE LADDER TO INSPECT METER BASE |