Permit: T07CM04372

Parcel: 14028035B


Addresses:

2385 E VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/26/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
BE ADVISED THERE ARE 2 OTHER NON-FINALED PERMITS OPEN AT THIS LOCATION, MUST BE APPROVED.
08/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK U.G., INSTALL MARKER TAPE IN TRENCH PER NEC. 300 FOR UTILITY POWER TO X-FORMER
07/24/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE SHEET METAL SCREWS FOR GROUND BAR ATTACHMENT
2. SERVICE CONDUCTORS NOT SIZED PROPERLY FOR 200 AMP SERVICE TO BE 3/0 COPPER
3. MAIN BONDING JUMPER AND OTHER BONDING JUMPERS NOT SIZED PROPERLY. PREVIOUS INSPECTION ITEM
4. AIC RATING TO BE 22 KAIC WHAT IS AVAILABLE FAULT CURRENT FROM TEP X-FMR
5. 2 1/2" PVC TO BE 24" DEEP MIN.
6. MARK SERVICE DISCONNECT
07/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MAIN BOND JUMPR AND BOND WIRE AHEAD OF OVERCURRENT PROTECTION TO BE SIZED PER 250.66 NEC & PER 250.28
07/17/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEUTRAL MUST BE BONDED WITH MAIN BOND JUMPER
PER 250 NEC - SEE NOTE #1 INSP. 7/14/08
07/14/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled
07/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL MAIN BONDING JUMPER IN SERVICE PANEL
2. PROVIDE LADDER TO INSPECT METER BASE