Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2008 | FIRE - FINAL | Approved | ||
| 03/03/2008 | FIRE - FINAL | Partial Approval | TEMP C OF O OK ---- NEED FOLLOWING AREAS CORRECTED 1.) Corridor #122 north end of corridor move smoke detector, to close to A/C vent must be 3 feet a way from all intake and exhaust. 2.) Install smoke detector in room where fire alarm panel is located, this is for the protection of the panel. 3.) Corridor #140 move smoke detectors 3' a way from all A/C vents, must be 3 feet a way from all intake and exhaust. 4.) Rooms 219 and 220 move strobes and horn from behind doors, blocking strobe lights. |
|
| 02/26/2008 | FIRE - FINAL | Partial Approval | OK for temp C of O #100 Southeast 1st floor |
|
| 02/13/2008 | FIRE - FINAL | Not ready for Inspection | Need alarm final |