Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T07CM04371

Parcel: 11011181B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
04/22/2008 FIRE - FINAL Approved
03/03/2008 FIRE - FINAL Partial Approval TEMP C OF O OK ---- NEED FOLLOWING AREAS CORRECTED
1.) Corridor #122 north end of corridor move smoke detector, to close to A/C vent must be 3 feet a way from all intake and exhaust.
2.) Install smoke detector in room where fire alarm panel is located, this is for the protection of the panel.
3.) Corridor #140 move smoke detectors 3' a way from all A/C vents, must be 3 feet a way from all intake and exhaust.
4.) Rooms 219 and 220 move strobes and horn from behind doors, blocking strobe lights.
02/26/2008 FIRE - FINAL Partial Approval OK for temp C of O
#100 Southeast 1st floor
02/13/2008 FIRE - FINAL Not ready for Inspection Need alarm final