Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM04371
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/17/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO CLOSE BOTTOM OF EXHAUST DUCTS FIRE WRAP PROGRESSING |
|
04/15/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CHECKED REMAINING WELDS ON GREASE DUCTS OK TO FIRE WRAP 1ST LAYER ACCESS DOORS - OK TO PROCEED |
|
03/24/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES ICE ROOM, SEWING ROOM, LOCKER ROOM |
|
03/20/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - SEE ENGINEER FOR RETURN OR TRANSFER AIR TO LOCKER ROOM AC - OK FOR CEILING TILES COLD STORAGE ROOM |
|
03/18/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
03/14/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CHECKED 1ST GREASE DUCT IN SHAFT OK TO PROCEED WITH 2ND DUCT. OK TO COVER HARD LID IN DINING ROOM. |
|
02/20/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | OK CEILING TILES 123, 124, 125, 133, 134, CORRIDOR 122 NEED RA TRANSFER ROOM 134 |
|
02/15/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* TESTED DUCT SMOKE DETECTORS 218-222, 223, 224, 217, 216, 215, 214, 213, 212, 211, 210, 209, 208, 207, CORRIDORS 206 & 201 SEE BLDG INSP. FOR TEMP C OF O |
|
02/13/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/06/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR SOUTH CORRIDOR OK FOR CEILING TILES |
|
01/31/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FIRE-RATED SHAFT REQUIRED FOR PENETRATION OF FIRE RATED FLOOR/CEILING ALL THE WAY THROUGH THE ROOF & MUST BE EQUAL TO EXISTING FIRE RATING. NOT NECESSARY TO FIRE WRAP GREASE DUCTS IN A FIRE RATED SHAFT. REVISE PLANS AS NEEDED. NEED TO TEST DUCT SMOKE DETECTORS SYSTEM IN SOUTH SIDE PHASE 1 |
|
01/28/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO PROCEED PROVIDE MIN. 20X30 ACCESS DOORS TO SERVICE FAN COILS ABOVE RESTROOMS |