Permit: T07CM04371

Parcel: 11011181B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/17/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
04/14/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CALL FOR AND HAVE APPROVED ALL INSP. PRIOR TO FINAL
ABV CEILING PIPING BEING RE-ROUTED AT HOOD LOCATIONS.
03/03/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
02/25/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
02/22/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RM 148 OK TO ONE SIDE - USE PROPER ADAPTOR FITTINGS

PROVIDE BUCKET FOR LEAK TESTING
PIPE INSULATION, SUPPORT, CLOSET CONNECTION AT WALL
02/14/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
TOILET RMS 159-160 OK
REVISE PLAN TO SHOW WH LOCATIONS
02/13/2008 PLUMBING - FINAL Cancelled
02/11/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ONLY ONE SLIP NUT ALLOWED DN STREAM OF P-TRAP
CORRECT DRIPS
BREAK OFF LOCK SCREW ON HB VAC BREAKER
SEAL THREADED OPENINGS W/APPROVED SEALANT
PROVIDE ACCESS TO WH FOR INSPECTION & SERVICE
02/01/2008 PLUMBING - FINAL Cancelled PER GRANT