Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM04371
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/17/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/16/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/10/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HEALTH DEPT. REQUIRED 5 HAND SINKS ADDED IN KITCHEN N/H DWV FOR HAND SINKS INSTALLED OK WATER TEST TO TEN FEET OK |
|
03/13/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GAS PIPING TEST OK PROVIDE PLAN REV. FOR CHANGES PROVIDE VALVES APPROVED FOR NG AT RTU'S DWV AT TRASH RM OK ROUGH & INTERMEDIATE PIPING COMPLETE PROVIDE CITY APPROVED REVISIONS FOR ALL CHANGES |
|
03/11/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2 1/2" WELD PIPE W/60 PSI TEST OK SUBJECT TO APPROVED PLAN REVISION. DWV AT CULINARY STORAGE AND ICE RM. OK |
|
03/07/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GREASE WASTE AND VENTS W/TEST OK ABOVE CEILING KITCHEN OK RM 148 WALLS OK GAS PIPING IN WALLS AND BELOW FLOOR OK |
|
02/28/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GT VENT THRU ROOF OK |
|
02/25/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CAULK DF CONN TO WALL TRS 202 & 204 OK TO USE TRS 130 & 131 OK TO USE PROVIDE EXPANSION TANK ON EXISTING WH RM 217 NEED TO SEE DW CONNECTIONS CORRIDOR 225 AND 201 OK ABV CEILING OK |
|
02/22/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/20/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RM 152 (ICE) OK TO COVER |
|
02/15/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RM 151, 146, 149 AND MIDDLE WALL IN RM 148 OK TO COVER |
|
02/14/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK TO ONE SIDE WALLS IN KIT. TEST TO VENT TIE IN CORRECT SLOPE AND 1/4 BEND BELOW FLOOR |
|
02/06/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DF PIPING AT 223 OK TO COVER |
|
01/30/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SINKS IN RM 223 OK 4" HARD CAP ABV CEILING IN RM 131 |
|
01/29/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/28/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RMS 202 AND 204 -- OK TO COVER RMS 158 AND 159 -- PLEASE HARD CAP EXISTING PIPING ABV CEILING MAINTAIN ACCESS TO ALL VALVES |
|
01/25/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LAVITORIES OK PROVIDE PLAN REVISION CORRECT SLOPE AT DF USE A COMBINATION WYE AND 1/8TH BEND TO EXTEND CO TORQUE ALL BANDS W/TORQUE WRENCH PROVIDE CLEARANCE AT SOV TO HAMMER ARRESTOR MAINTAIN ACCESS TO EXISTING SOV BRR RM SINK OK 217 |
|
01/24/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | TRS 202 & 204 SUPPORT OVERHEAD COPPER |
|
01/23/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSULATION OK PER SPEC 15 400 #2G TRS 130 & 131 OK TO COVER |
|
01/22/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TR RMS 158-159 OK TO COVER PIPES INSULATED WITH 1/2 ARMORFLEX |
|
01/18/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* AFTR HRS INSP FOR GRANT 801-502-4050 PAID W/MONEY ORDER #08 807890219 WATER TEST OK SUPPORT PIPING AT URINALS & DFS INSTALL LISTED PIPE CLAMPS INSULATE PIPE PER PLAN SPECS. PROVIDE HAMMER ARRESTORS PROVIDE TRAP SEAL PROTECTION HARD CAPS ON TEST WYE & END OF RUN BELOW FLOOR QUALIFIED MECHANICAL HAS BEEN TOLD THAT DEBURRING COPPER TUBE AND THE REMOVAL OF EXCESS FLUX IS REQUIRED BY CODE AND WILL BE ENFORCED. |