Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04371
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUNDING ELECTRODE SYSTEM FOR SEPARATELY DERIVED SYSTEM 2. BOND FLEX RACEWAYS TO TRANSFORMER 3. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANEL 4. PROTECT SEALTITE FROM SHARP METAL EDGES 5. LABEL DISCONNECTS 6. BOND BUSHINGS 250.97 7. MAINTAIN WORKING CLEARANCES 110.26 8. TIGHTEN LOOSE FITTINGS 9. FINISH #2 & #6 PREVIOUS INSPECTION |
|
04/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" (314.20) OR 1/8" (314.21) 2. USE APPROVED FITTINGS WITH CORDS 3. GROUND DEVICE BOXES 4. RECEPTACLES TO BE GFCI PROTECTED 210.8(B) 5. ATTACH FIXTURES TO GRID 410.16 6. PANEL DIRECTORIES TO BE PERMANENT AS PER 408.4 |
|
03/04/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
03/03/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 2ND FROM EM LIGHT |
|
02/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EM LIGHT IN HALL NOT WORKING 2ND FLOOR 2. NEED REVISION TO PLANS FOR CHANGE IN LIGHTING CIRCUITRY 3. WILL NEED PANEL SCHEDULES 4. OK PARTIAL FINAL ROOMS 123, 122, 127, 128, 129, 130, 131, 132, 201 THRU 224 |
|
02/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
02/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/8" 314.21 OR MORE THAN 1/4" - 314.20 2. ID TAPE TO ENCIRCLE CONDUCTOR 3. ROOMS - EM LIGHTING TO BE AS PER 700.12 4. MAINTAIN WORKING CLEARANCES 110.26 5. FINISH DATA ROOM |
|
02/01/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |