Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04371
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/18/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/17/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK KITCHEN SOUTH TO 5' FROM HOOD 1. PLEASE VERIFY PLENUM RATING FOR MOTION SENSOR EQUIPMENT |
|
04/15/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
04/14/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FILL UNUSED CONDUIT OPENINGS 2. SUPPORT VDV CABLING - CONDUITS NOT A SUPPORT POINT 3. VERIFY USAGE & SPLICES IN A PLENUM FOR MOTION SENSORS OK DINING LAB AND NORTH KITCHEN EXCEPT AS NOTED |
|
04/11/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* FINISH GRID WORK & WIRES |
|
03/24/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 137, 138 EXCEPT AS NOTED 1. DISCONNECT 110.26 |
|
03/21/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. GROUND JUNCTION BOXES 2. BOX BROKEN 3. DIE ELECTRIC |
|
03/18/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAINTAIN WORKING CLEARANCE AT DISCONNECT 2. CONDUIT CANNOT SUPPORT WATER LINES 3. WHAT ARE HANGING MC CABLES? |
|
03/17/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
03/14/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/12/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/21/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILINGS RMS 123, 124, 125, 134, 133 & CORRIDOR 122, 132 |
|
02/20/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
02/15/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* VDV CABLING TO BE AS PER 725.6 - APPROVED METHODS IN A NEAT AND WORKMANLIKE MANNER OK ELECTRIC LIGHTS & CONDUITS 2 NORTHWEST |
|
02/13/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HALL AND CLASSROOMS 2 NORTHEAST OK 1 SOUTH EAST |
|
02/06/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. EXCESS M/C COILED ABOVE CEILING OK HALLS SOUTHEAST 1ST FLOOR AFTER CORRECTION |
|
01/31/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* DO NOT TILE OR DRYWALL UNTIL APPROVED 1. BOX OVERFILLED - MAKE UP CONDUCTORS 2. FILL UNUSED OPENINGS - NOT FITTINGS OK 2ND FLOOR BATHROOMS - NORTH END |
|
01/30/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/29/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* OK WOMENS BATH SOUTH 1ST FLOOR 1ST FLOOR: 1. MENS ROOM SOUTH HALF: ACCESS FOR JUNCTION BOXES AND CLOSE BOXES 2. FILL UNUSED OPENING IN BOXES 3. FINISH VDV CABLING 4. BOX OVERFILLED 5. RESUPPORT CONDUIT 6. BOND OVER 250V - 250.97 |
|
01/28/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |