Permit: T07CM04371

Parcel: 11011181B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/22/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/18/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/17/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK KITCHEN SOUTH TO 5' FROM HOOD

1. PLEASE VERIFY PLENUM RATING FOR MOTION SENSOR EQUIPMENT
04/15/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED
04/14/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FILL UNUSED CONDUIT OPENINGS
2. SUPPORT VDV CABLING - CONDUITS NOT A SUPPORT POINT
3. VERIFY USAGE & SPLICES IN A PLENUM FOR MOTION SENSORS

OK DINING LAB AND NORTH KITCHEN EXCEPT AS NOTED
04/11/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
FINISH GRID WORK & WIRES
03/24/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 137, 138 EXCEPT AS NOTED

1. DISCONNECT 110.26
03/21/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. GROUND JUNCTION BOXES
2. BOX BROKEN
3. DIE ELECTRIC
03/18/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MAINTAIN WORKING CLEARANCE AT DISCONNECT
2. CONDUIT CANNOT SUPPORT WATER LINES
3. WHAT ARE HANGING MC CABLES?
03/17/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED
03/14/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/12/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/21/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILINGS RMS 123, 124, 125, 134, 133 & CORRIDOR 122, 132
02/20/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
02/15/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
VDV CABLING TO BE AS PER 725.6 - APPROVED METHODS IN A NEAT AND WORKMANLIKE MANNER

OK ELECTRIC LIGHTS & CONDUITS 2 NORTHWEST
02/13/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HALL AND CLASSROOMS 2 NORTHEAST
OK 1 SOUTH EAST
02/06/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. EXCESS M/C COILED ABOVE CEILING

OK HALLS SOUTHEAST 1ST FLOOR AFTER CORRECTION
01/31/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
DO NOT TILE OR DRYWALL UNTIL APPROVED

1. BOX OVERFILLED - MAKE UP CONDUCTORS
2. FILL UNUSED OPENINGS - NOT FITTINGS

OK 2ND FLOOR BATHROOMS - NORTH END
01/30/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/29/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
OK WOMENS BATH SOUTH 1ST FLOOR

1ST FLOOR:
1. MENS ROOM SOUTH HALF: ACCESS FOR JUNCTION BOXES AND CLOSE BOXES
2. FILL UNUSED OPENING IN BOXES
3. FINISH VDV CABLING
4. BOX OVERFILLED
5. RESUPPORT CONDUIT
6. BOND OVER 250V - 250.97
01/28/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*