Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04371
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CONDUITS AT PANEL OK CAN 149 OK GRID 152-157, 147 |
|
03/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUITS ABOVE PANEL ABOVE CEILING 1. FILL UNUSED OPENINGS 2. DISCONNECTS NOT ALLOWED HORIZONTAL 3. SUPPORT CONDUIT 3' *300.7 WILL APPLY FOR WALK IN BOXES 4. MANUFACTURE CLIPS TO BE EFFECTIVE 5. JUNCTION BOXES TO BE ACCESSIBLE 6. NO MORE THAN 300V BETWEEN DEVICES IN BOXES |
|
02/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOM #147 OK HARD LIDS FOR SOFFITS IN CORRIDOR |
|
02/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/20/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER ROOMS #150 THROUGH #155 AND HALL #148 |
|
02/19/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DRYWALL AND INSULATION TO BE REMOVED FOR INSPECTION UPSTAIRS STAT HAS BEEN SUPPORTED |
|
01/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NORTH BATHROOM MENS: *5TH TIME TO MAKE BOX ACCESSIBLE OR REMOVE CONDUCTORS AND SUPPORT CABLING (T-STAT WIRE) A REFEE MAY BE ASSESSED IF NOT COMPLETED OK HALLS SOUTHEAST OK HARD LID SOUTH HALL OK 2X4's ROOM 142-146 OK WOMENS BATH NORTH MENS & WOMENS SOUTH |
|
01/28/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK LOBBY SOUTH 1/2 OK 2ND FLOOR HALLS 1. SUPPORT FLEX CONDUITS AT BOTH ENDS - 300.11 2. JUNCTION BOXES TO BE ACCESSIBLE 3. CAN JUNCTION BOX OVER FILLED 4. FINISH VDV CABLING |
|
01/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. FINISH VDV CABLING 2. NOTE 400.7 & 8 FOR CORDS 3. EQUIPMENT ELECTRICAL CONNECTION NEEDS TO BE ACCESSIBLE 4. BUILDING INSPECTOR TO LOOK AT FIRE STOPPING OK CANS HALL EXCEPT NORTH END 1ST FLOOR SOUTH END 1ST FLOOR EAST HALL MIDDLE LOBBY |
|
01/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONTR. REQUEST AFTER HRS. INSP. PAID $150.00 MONEY ORDER #08-807890217 OK WALLS ONLY ROOM #'S -- 159, 160, 140, 141, 142, 143, 144, 145, 146 OK WALLS 2ND FLOOR - 123, 124, 125, 129, 130, 131, 132, 133, 134, WALLS 1ST FLOOR |