Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM04366
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/20/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/30/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL BUSHINGS ON 1 1/4 CONNECTORS FOR NEW LUGS BOLTED TO BUSS IN PANEL "B" NOT FLAT AGAINST BUSS. THIS METHOD MAY VOID LISTING OF PANEL. PROVIDE U.L FIELD EVALUATION FOR ACCEPTANCE. SUB-PANEL FEED. AS PER NEC. CUTTING OFF CONDUCTOR STRANDS FOR NEUTRAL FEEDER NOT ALLOWED, DOUBLE LUGGING NOT ALLOWED PER LISTING & NEC (PANEL "B") 2. PANEL "A" HAS 50 AMP. 2P BREAKER FEEDING #10 CONDUCTORS ALSO, #10 GROUN SPLICED TO #12 IN PANEL? SHEETMETAL SCREWS NOT APPROVED TO GROUND EQUIP. PER 250 NEC. 3. NEED TO VERIFY INTERLOCKS ARE WORKING FOR EXH. FANS 4. PLANS CALL FOR 15 AMP BREAKERS FOR NEW PANEL "BA" CONTROL CIRCUITS 5. OBTAIN THE SERVICES OF A QUALIFIED OR LICENSED ELECTRICIAN TO DO THE WORK CONTR. REQUEST RETURN INSP. AFTER HRS. $150.00 FEE PAID CK#61938 |
|
| 05/29/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/28/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUIT WITHIN 3' OF TERMINATION AND AT 10' INTERVALS PER NEC 2. CLARIFY PLAN NOTES FOR PANEL "EM"? COULD NOT LOCATE 3. I.D FA CONDUITS BOXES PER NEC 4. WIRING TO ELEVATOR CONTROL CABINETS NOT PER PLAN 5. CONDUIT/WIRING NOT COMPLETE FOR EXH. FAN INTERLOCKS, FIRE, SMOKE SENSORS NOT COMPLETE |