Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM04366

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/25/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/20/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/30/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. INSTALL BUSHINGS ON 1 1/4 CONNECTORS FOR NEW
LUGS BOLTED TO BUSS IN PANEL "B" NOT FLAT AGAINST BUSS. THIS METHOD MAY VOID LISTING OF PANEL. PROVIDE U.L FIELD EVALUATION FOR ACCEPTANCE. SUB-PANEL FEED. AS PER NEC. CUTTING OFF CONDUCTOR STRANDS FOR NEUTRAL FEEDER NOT ALLOWED, DOUBLE LUGGING NOT ALLOWED PER LISTING & NEC (PANEL "B")
2. PANEL "A" HAS 50 AMP. 2P BREAKER FEEDING #10 CONDUCTORS ALSO, #10 GROUN SPLICED TO #12 IN PANEL?
SHEETMETAL SCREWS NOT APPROVED TO GROUND EQUIP. PER 250 NEC.
3. NEED TO VERIFY INTERLOCKS ARE WORKING FOR EXH. FANS
4. PLANS CALL FOR 15 AMP BREAKERS FOR NEW PANEL "BA" CONTROL CIRCUITS
5. OBTAIN THE SERVICES OF A QUALIFIED OR LICENSED ELECTRICIAN TO DO THE WORK

CONTR. REQUEST RETURN INSP. AFTER HRS. $150.00 FEE
PAID CK#61938
05/29/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/28/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT CONDUIT WITHIN 3' OF TERMINATION AND
AT 10' INTERVALS PER NEC
2. CLARIFY PLAN NOTES FOR PANEL "EM"? COULD NOT LOCATE
3. I.D FA CONDUITS BOXES PER NEC
4. WIRING TO ELEVATOR CONTROL CABINETS NOT PER PLAN
5. CONDUIT/WIRING NOT COMPLETE FOR EXH. FAN INTERLOCKS, FIRE, SMOKE SENSORS NOT COMPLETE