Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04358
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/28/2008 | ELECTRIC - FINAL | Approved | SEALED LETTER FROM ENGINEER ALLOWING BATTERY BACK UP TROFFERS AND DELETION OF EXPANSION COUPLING RECIEVED AND FILED. | |
05/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PLANS CALL FOR EXPANSION COUPLINGS AND EM FLOODS HAVE ENGINEER ADDRESS THESE |
|
05/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATIONS, DISTINGUISHABLE FROM ONE ANOTHER AND PERMANENT 2. LABEL OUTSIDE OF COVER ON PANELS 3. INSTALL MAIN BONDING JUMPER 4. CANNOT STACK LUGS 5. NEED REJECTION PINS 6. IDENTIFY IG GROUNDS WITH YELLOW MARKINGS 7. SEAL TO BE NON-COMBUSTIBLE 8. EXIT LIGHTS TO BE AS PER 700.12 ROOF: 9. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8 10. TIGHTEN ALL LOOSE FITTINGS 11. PROTECT CATV CABLE UPON ENTRY OF CONDUITS AND NEED TO BE WEATHERPROOF 12. SUPPORT CATV CABLES 13. BOND CONDUCTOR NEEDED FOR CATV/SATELLITE DISH SYSTEMS 14. ALL KITCHEN RECEPTACLES TO BE GFI PROTECTED |