Inspection History: ELECTRIC - FINAL

Permit Number - T07CM04358

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/28/2008 ELECTRIC - FINAL Approved SEALED LETTER FROM ENGINEER ALLOWING BATTERY BACK UP TROFFERS AND DELETION OF EXPANSION COUPLING RECIEVED AND FILED.
05/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PLANS CALL FOR EXPANSION COUPLINGS AND EM FLOODS
HAVE ENGINEER ADDRESS THESE
05/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORIES TO BE AS PER 408.4 -
NO ABBREVIATIONS, DISTINGUISHABLE FROM ONE ANOTHER AND PERMANENT
2. LABEL OUTSIDE OF COVER ON PANELS
3. INSTALL MAIN BONDING JUMPER
4. CANNOT STACK LUGS
5. NEED REJECTION PINS
6. IDENTIFY IG GROUNDS WITH YELLOW MARKINGS
7. SEAL TO BE NON-COMBUSTIBLE
8. EXIT LIGHTS TO BE AS PER 700.12

ROOF:
9. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8
10. TIGHTEN ALL LOOSE FITTINGS
11. PROTECT CATV CABLE UPON ENTRY OF CONDUITS AND NEED TO BE WEATHERPROOF
12. SUPPORT CATV CABLES
13. BOND CONDUCTOR NEEDED FOR CATV/SATELLITE DISH SYSTEMS
14. ALL KITCHEN RECEPTACLES TO BE GFI PROTECTED