Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04358
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/22/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE *406.3(D) |
|
04/21/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. VDV CABLING TO BE SUPPORTED 725.24, 800.24, 300.11 *210.8 WILL APPLY FOR CHANGED OUT RECEPTACLES |