Permit: T07CM04351

Parcel: 10818716A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T07CM04351

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/03/2007 FIRE - FINAL Approved
11/26/2007 FIRE - FINAL Denied REMOVE TAPE FROM SPR. HEADS. COVER PLATES FOR SPR. HEADS MUST FIT. EXHAUST FANS MUST KEEP RUNNING DURING HOOD TEST. ELECT RECEPT. NOT SHUTTING OFF. NEED 8" SPLASH GUARD ON FRYER FOR #3 SYSTEM. "K" EXT. NEEDS SERVICE & 5 YR HYDRO TEST. BELL/FLOW SWITCH NOT WORKING. REMOVE PIGTAILS FROM CONTROL BOX.