Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T07CM04351
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2007 | FIRE - FINAL | Approved | ||
11/26/2007 | FIRE - FINAL | Denied | REMOVE TAPE FROM SPR. HEADS. COVER PLATES FOR SPR. HEADS MUST FIT. EXHAUST FANS MUST KEEP RUNNING DURING HOOD TEST. ELECT RECEPT. NOT SHUTTING OFF. NEED 8" SPLASH GUARD ON FRYER FOR #3 SYSTEM. "K" EXT. NEEDS SERVICE & 5 YR HYDRO TEST. BELL/FLOW SWITCH NOT WORKING. REMOVE PIGTAILS FROM CONTROL BOX. |