Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04351
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION 1. IDENTIFY PANEL DIRECTORY'S IN OFFICE - NOT A PIECE OF PAPER 2. ALL NEW WIRING TO BE SUBMITTED TO PLAN REVIEW |
|
11/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HOOD/INTERLOCK WIRING TO BE CORRECTED PER T.F.D 2. ALL 12OV KITCHEN RECEPTACLES TO HAVE GFI PROTECTION 210.8 B2 3. CORRECTLY IDENTIFY PANEL DIRECTORY - 408.4 4. WIRING FOR RECEPTACLES NOT PER PLAN, ALSO APPEARS TO HAVE BEEN COVERED BEFORE INSPECTION 5. MC IN CEILING TO BE SUPPORTED @ MAX 6' INTERVALS NEC 330.30, CEILING GRID SUPPORT WIRES NOT TO BE USED 300.11 |