Permit: T07CM04351

Parcel: 10818716A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PARTIAL INSPECTION
1. IDENTIFY PANEL DIRECTORY'S IN OFFICE - NOT A PIECE OF PAPER
2. ALL NEW WIRING TO BE SUBMITTED TO PLAN REVIEW
11/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HOOD/INTERLOCK WIRING TO BE CORRECTED PER T.F.D
2. ALL 12OV KITCHEN RECEPTACLES TO HAVE GFI
PROTECTION 210.8 B2
3. CORRECTLY IDENTIFY PANEL DIRECTORY - 408.4
4. WIRING FOR RECEPTACLES NOT PER PLAN, ALSO APPEARS TO HAVE BEEN COVERED BEFORE INSPECTION
5. MC IN CEILING TO BE SUPPORTED @ MAX 6' INTERVALS
NEC 330.30, CEILING GRID SUPPORT WIRES NOT TO BE
USED 300.11