Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/13/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/12/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* FINISH PREVIOUS ITEMS - ANSWERED QUESTIONS |
|
| 12/11/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 12/10/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* TILES STILL IN |
|
| 12/10/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. RE-SUPPORT CONDUITS 2. VDV CABLING TO BE AS PER 725.3, 800.3 FOR ABANDONED CABLES AND 300.11 FOR SUPPORTED CABLES LEAVE AREAS OPEN TO CHECK AT FINAL OK TO TILE EXCEPT AS NOTED *NEED PLAN REVISION FOR PANELS & CIRCUITS NEED CURRENT GENERATOR REPORT RECEIVED CHK#3158 FOR $150.00 |
|
| 12/07/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* OPEN ALL TILE TO INSPECT |
|
| 12/06/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELLED |