Permit: T07CM04350

Parcel: 12701005D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM04350

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/13/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/12/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
FINISH PREVIOUS ITEMS - ANSWERED QUESTIONS
12/11/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELLED
12/10/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
TILES STILL IN
12/10/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. RE-SUPPORT CONDUITS
2. VDV CABLING TO BE AS PER 725.3, 800.3 FOR ABANDONED CABLES AND 300.11 FOR SUPPORTED CABLES
LEAVE AREAS OPEN TO CHECK AT FINAL

OK TO TILE EXCEPT AS NOTED

*NEED PLAN REVISION FOR PANELS & CIRCUITS
NEED CURRENT GENERATOR REPORT

RECEIVED CHK#3158 FOR $150.00
12/07/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
OPEN ALL TILE TO INSPECT
12/06/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELLED