Permit: T07CM04347

Parcel: 14029051A

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Permit Number - T07CM04347

Inspection Description - PLUMBING - GAS PRESS TEST FNL

Inspection Status - Approved

Date Description Inspector Results Comments
11/19/2008 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
11/14/2008 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
11/10/2008 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*
4" GAS PIPING TO BACK UP GENERATOR TEST OK
11/06/2008 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
TEST NOT HOLDING FOR OUTSIDE PIPING
10/29/2008 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*
1. ADD SUPPORT ON WEST END OF BUILDING FOR GAS AND PROVIDE APPROVED SUPPORT ON ROOF
2. COMPLETE GAS PIPING TO BACK UP GENERATOR
3. PSI TEST STUB OUT OF BLD. TO ROOF