Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2009 | MECHANICAL - ABOVE CEILING | Approved | ||
| 12/08/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) DUCT NOT SIZED PER PLANS 2) TAPE ACCEPTABLE AS DUCT SEALER, REMOVE TAPE AND SEAL PER MECH SPECS 3) PROVIDE DUCT CONSTRUCTION PER SMACNA STANDARDS 4) ROUND BRANCH TAPS TO HAVE ? PER SPECS 5) ALL DUCT/SYSTEM CHANGES TO BE APPROVED BY ENGINEER |