Permit: T07CM04342

Parcel: 117120220


Addresses:

61 E CONGRESS ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/21/2009 MECHANICAL - ABOVE CEILING Approved
12/08/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) DUCT NOT SIZED PER PLANS
2) TAPE ACCEPTABLE AS DUCT SEALER, REMOVE TAPE AND SEAL PER MECH SPECS
3) PROVIDE DUCT CONSTRUCTION PER SMACNA STANDARDS
4) ROUND BRANCH TAPS TO HAVE ? PER SPECS
5) ALL DUCT/SYSTEM CHANGES TO BE APPROVED BY ENGINEER