Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2010 | EXCAVATION/LAYOUT REBAR & ZON | Approved | ||
| 03/10/2009 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | STAIR FOOTINGS REINSTALLED PER PLAN. OK TO PLACE CONCRETE. | |
| 03/07/2009 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | #6 VERTICALS INSTALLED WITH ONLY 24" LAP SPLICE INSTEAD OF 66" PER PLAN. #5 AND #6 STEEL INSTALLED IS 40 KSI INSTEAD OF PLAN REQUIRED 60 KSI. INSTALLER HAS PUT IN TOP MAT OF REINFORCING THAT IS NOT ON PLAN. SUPERINTENDENT NOTIFIED THAT NEW CALCULATIONS WOULD BE REQUIRED FOR CHANGES TO FOOTING. ANY CONCRETE PLACEMENT WOULD BE AT HIS OWN RISK. |
|
| 03/06/2009 | EXCAVATION/LAYOUT REBAR & ZON | Denied | 1) MISSING #6 VERTICALS PER KEYNOTE 5 PP S1.1. 2) MISPLACED AND MISSING TOP BARS IN FOOTING PER DETAILS 8 & 9 PP S1.3. 3) CONTRACTOR UNAWARE OF REQUIREMENT FOR SPECIAL INSPECTIONS NOTED IN GSN's AND REQUIRED BY CHAPTER 17 OF THE IBC. |