Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 12/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MC NOT ATTACHED TO AT BOTH ENDS 300.11 #3 PREVIOUS |
|
| 12/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH PREVIOUS ITEMS |
|
| 12/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 AND MORE THAN 1/8" TO EDGE - 314.21 2. WE HAVE EXCESS PAINT ON DEVICE TERMINALS - 110.12 3. SUPPORT M/C CABLE ABOVE CEILING - 330.30 |