Permit: T07CM04327

Parcel: 12801005H

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T07CM04327

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2008 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
04/29/2008 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. EXTEND VENT THRU ROOF
2. PROVIDE INSULATION ON PIPING PER PLAN
3. SUPPORT HOT WATER PIPING FOR MOP SINK PROPERLY
(TIE WIRE IS NOT) PRIOR TO COVERING
04/11/2008 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*