Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM04327
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXITS AND EM LIGHTS STILL NOT WORKING 2. CANNOT USE SHEETMETAL SCREWS FOR CONNECTION OF GROUND BARS PANELS/AC DISCONNECT 3. ONE WIRE TO TERMINATE TO LUG BONDING BUSHING AC DISCONNECT |
|
06/06/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* CORRECTIONS MADE AS NOTED BY INSPECTION RICHARD JIROUDEK WHO AUTHORIZED THIS APPROVAL. |
|
06/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE TEMP POWER FROM STORAGE RM CEILING 2. INSTALL COVER ON BOX STORAGE RM CEILING 3. INSTALL MISSING PLATES (UP FRONT RECEPS) 4. BATHROOM RECEPT TO BE GFI PROTECTED 5. NEED DISCONNECTING MEANS FOR WATER HEATER 6. GROUNDS & NEUTRALS TO BE SEPARATE AT PANELS INSTALL GROUND BARS IN PANELS 7. REMOVE MAIN BONDING JUMPERS 8. SEPARATE GROUNDS XFMR 9. MARK PHASE CONDUCTORS 277/480V COLORS 10. CHECK EXITS & EMS TO BE WORKING PROPERLY 11. INSTALL EQUIPMENT GROUND TO AC UNIT 12. INSTALL BONDING BUSHING ON CONNECTIONS TO AC DISCONNECT 13. FUSES OVERSIZED FOR AC UNIT 14. ROOFTOP GFI HAS NO POWER |
|
06/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ALL ITEMS FROM CEILING INSPECTION ON 5/20/08 HAVE MORE CEILING TILES REMOVED FOR INSPECTION 2. NO FINAL INSPECTION UNTIL CEILING PASSES |