Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04327
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/04/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/29/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE CEILING TILES FOR INSPECTION |
|
05/20/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TIE WIRES ON LIGHT FIXTURES 2. LIGHT FIXTURES TO BE ATTACHED TO CEILING GRID 3. CLOSE OPEN JUNCTION BOXES 4. SEAL OPEN KNOCK OUTS 5. STRAP MC WITHIN 12" OF JUNCTION BOXES 6. MC CABLES TO BE SUPPORTED EVERY 6' DO NOT USE CEILING TIE WIRES 7. STRAP 2" EMT EVERY 10' 8. DO NOT USE DUCT WORK FOR SUPPORT OF JUNCTION BOXES 9. SUPPORT FIRE ALARM WIRE EVERY 6'. ALL LOW VOLTAGE 10. HAVE OPEN WIRING INTO CEILING BY WATER HEATER 11. STRAP EMT TO ROOFTOP UNIT 12. FINISH FIRE ALARM SYSTEM |
|
04/25/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LIDS SALES FLOOR |
|
04/24/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
04/23/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* OK WALLS BATHROOMS |
|
04/16/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/11/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |