Permit: T07CM04327

Parcel: 12801005H

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM04327

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/05/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/04/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/29/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
REMOVE CEILING TILES FOR INSPECTION
05/20/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TIE WIRES ON LIGHT FIXTURES
2. LIGHT FIXTURES TO BE ATTACHED TO CEILING GRID
3. CLOSE OPEN JUNCTION BOXES
4. SEAL OPEN KNOCK OUTS
5. STRAP MC WITHIN 12" OF JUNCTION BOXES
6. MC CABLES TO BE SUPPORTED EVERY 6' DO NOT USE CEILING TIE WIRES
7. STRAP 2" EMT EVERY 10'
8. DO NOT USE DUCT WORK FOR SUPPORT OF JUNCTION BOXES
9. SUPPORT FIRE ALARM WIRE EVERY 6'. ALL LOW VOLTAGE
10. HAVE OPEN WIRING INTO CEILING BY WATER HEATER
11. STRAP EMT TO ROOFTOP UNIT
12. FINISH FIRE ALARM SYSTEM
04/25/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HARD LIDS SALES FLOOR
04/24/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/23/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
OK WALLS BATHROOMS
04/16/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/11/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*