Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/24/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPERLY STRAP MC CABLE ABOVE HARD LID. USE SINGLE CONNECTORS WHERE ONE CABLE ENTERS FIXTURE 2. RECALL WHEN READY. NEEDS TO BE READY TO AVOID REFEE |
|
| 04/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL MUD RINGS & GROUNDING BOXES BACK OF STORE MISSING K.O IN BOXES 2. OK WALLS SALES FLOOR 3. OK HARD LIDS SALES FLOOR EXCEPT AREAS MISSING FIXTURES 4. RECALL FOR WALLS BACK OF STORE - WHEN READY |
|
| 04/11/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* RECALL WHEN WORK COMPLETE AND READY FOR INSPECTION |