Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WIRING TO INVERTERS @ PADS G & H 2. RECEIVED COPY OF GFI PERFORMANCE TEST |
|
| 10/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK 4 POLE BASES 2. OK INVERTORS A TO F 3. OK TO ENERGIZE SUBSTATION #6 WHEN GFI PERFORMANCE TEST COMPLETE AND PASSED |
|
| 10/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUB-STATION #6 INSPECTION 2. RECEIVED LETTER OF TORQUE, LETTERS FOR LISTING 3. NEED MAIN GFI TEST PER 230.95 NEC 4. CONSULT WITH RICHARD JIROUDEK FOR BREAKER ARRANGEMENT AT LOAD |
|
| 10/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SES-1: RECEIVED LETTER OF TORQUE - EQUIPMENT IS SECURED TO PAD. TERMINATIONS OK - GROUND RING & CADWELDS & RODS OK WAITING ON HIGH POT TESTING NO CONNECTIONS TO SOLAR FIELD RECEIVED CK#382761 - $150.00 |
|
| 10/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK GROUND RING AT SUBSTATION #6 |
|
| 10/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONTR. TO RECALL, NEED INSPECTION TO FAMILIARIZE WITH SAT-OUTAGE |