Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/29/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE NEW DATA PLATES TO REPLACE THE DESTROYED ONES ON 4 AC UNITS 5 TON UNITS NOT FUSED CORRECTLY I.D 5 TON UNITS PROVIDE AIR BALANCE REPORT PROVIDE BUSHINGS IN AC PANELS |
|
| 10/23/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE FUSES IN ALL ELEC. DISCONNECTS 2. PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS 3. MARK UNIT DATA PLATES & FUSE ACCORDINGLY 4. SUPPORT DUCT SMOKE DETECTOR SENSING TUBES 5. PROVIDE INSTALL INSTRUCTIONS 6. SECURE MINI-SPLIT CONDENSORS 7. PERMANENTLY I.D ROOF TOP EQUIPMENT |
|
| 10/14/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* USE APPROVED HANGER STRAPS |