Permit: T07CM04318

Parcel: 135074560


Addresses:

1800 S RESEARCH LP


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM04318

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/29/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE NEW DATA PLATES TO REPLACE THE DESTROYED ONES ON 4 AC UNITS
5 TON UNITS NOT FUSED CORRECTLY
I.D 5 TON UNITS
PROVIDE AIR BALANCE REPORT
PROVIDE BUSHINGS IN AC PANELS
10/23/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE FUSES IN ALL ELEC. DISCONNECTS
2. PROVIDE AUDIBLE & VISIBLE ALARMS FOR DUCT SMOKE DETECTORS
3. MARK UNIT DATA PLATES & FUSE ACCORDINGLY
4. SUPPORT DUCT SMOKE DETECTOR SENSING TUBES
5. PROVIDE INSTALL INSTRUCTIONS
6. SECURE MINI-SPLIT CONDENSORS
7. PERMANENTLY I.D ROOF TOP EQUIPMENT
10/14/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
USE APPROVED HANGER STRAPS