Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM04318
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* WATER DISTRIBUTION OK |
|
08/04/2008 | PLUMBING - INTERMEDIATE | Partial Approval | DWV THRU ROOF WATER TEST ALL AREAS OK WATER DISTRIBUTION FROM METER THRU EAST CENTER SERVICE ENTRANCE THRU RESTROOM WITH 1" STUBS FOR FUTURE OK |
|
07/02/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* THIS INSPECTION FOR REVISED APPROVED PLAN OF 03040 YARD WATER IS OK |
|
06/19/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* THERE IS A CONFLICT BETWEEN P1.2 AND DP.2 FOR SIZING AND MATERIAL TYPE FOR WATER SERVICE AT EAST SIDE CENTER LOCATION. 2" METER, RPB & 2" PVC SCH 40 IS INSTALLED AND TESTED PER P1.2, DP2 REQUIRES 3" PVC SCH80. INSTALL PER APPROVED PLAN OR HAVE CITY REVISED PLAN |
|
06/05/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* THIS INSPECTION FOR 03040 3" FROM METER THRU RPB INTO BLD. 2' AFF AT NORTHWEST CORNER OK |