Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK EM LIGHTING 2. GROUND LIGHT POLES AND BOND RACEWAYS @ LIGHT POLES 3. NEED DISCONNECTING MEANS FOR DOCK LEVELERS & SUMP PUMPS TO BE WITHIN SIGHT OF EQUIPMENT SERVED 4. NEED PLAQUES @ SERVICES FOR MULTIPLE SERVICE LOCATIONS |
|
| 12/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. REVISE PLANS FOR SCOPE OF WORK, OUTDOOR LIGHTING, DELETING OF PLANS/X-FMRS 2. SOME EM LIGHTS IN FABRICATION NOT WORKING 3. NEED BONDING BUSHINGS ROOF TOP DISCONNECTS 480V 4. STAIRWELL EM LIGHT NOT WORKING 5. NEED PROPER WORKING CLEARANCE 2ND FLOOR ELECTRIC ROOM 6. STILL NEED TO INSPECT SOUTH END OF BUILDING |
|
| 12/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* VIEWED 1" ELEC. UNDERGROUND CONDUIT @ DOCK SUMP PIT OK |
|
| 10/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FRONT OFFICES 1. EXITS & EMS NOT PER PLAN 2. NEED BOX EXTENSIONS 3. PANEL SCHEDULES AND LABELING @ PANELS OPEN PANELS FOR INSPECTION 4. SOME RECEPT. NO POWER |