Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T07CM04318
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
07/15/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PVC RACEWAYS UNDER SIDEWALK NORTHWEST CORNER OF BUILDING |
|
06/25/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 5 - 4" PVC FROM FUTURE SES TO TEP XFMR WEST SIDE OF BUILDING |
|
06/02/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK PVC U.G AT LOADING DOCK 2. OK 2 POLE BASES 3. OK U.G FROM ISLAND TO ISLAND SEE E1.1 |
|
05/27/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PVC CONDUITS AS MARKED ON OFFICE PLANS B1.1 |
|
05/13/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK COMPLETION OF U.G PVC IN BUILDING |
|
04/08/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 1" PVC ALONG EAST WALL FOR PARKING LOT LIGHTING 2. OK 5 - 2 1/2" PVC ALONG WEST WALL FOR FUTURE POWER 3. OK 5 - 1 1/4" PVC ALONG WEST WALL FOR FUTURE TELEPHONE |
|
03/13/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 8 FLOOR BOXES & ASSOCIATED PVC |
|
03/10/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK U.G FOR PANEL FEEDERS |
|
03/07/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 7 - 4" PVC FROM SES TO DS-2 2. OK 4 - 4" PVC FROM SES TO DS-1 3. OK 2 - 2" PVC FROM DS-2 TO HOFC1 4. OK 2 - 2" PVC FROM DS-2 TO HF2 5. OK 2 - 2" PVC FROM DS-2 TO HOFC2 6. OK 4 - 2" PVC FROM DS-2 WEST 80' 7. OK 4 - 2" PVC FROM DS-2 NORTH 80' 8. OK 2 - 2" PVC FROM DS-2 TO HFI |
|
02/29/2008 | ELECTRIC - UNDERGROUND | Cancelled | IVRS - RI canceled | |
02/19/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 11 - 4" PVC FROM SES TO JUST PAST DEMISING WALL |
|
02/15/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 13 - 4" PVC FROM SES TO TEP XFMR 2. INSTALL WARNING RIBBON PER NEC 300.5 3. PROVIDE REVISION FOR CHANGE IN SERVICE CONDUCTORS FROM COPPER TO AL |